序号设备功率Pe(kW)需要系数Kx功率因数CosΦ功率因数的tanΦ有功功率(kW)无功功率(kvar)视在功率(kVA)备注争议项130.00.800.800.7524.0018.0030.00260.00.600.800.7536.0027.0045.00火灾时安防需继续运行,不能切除350.00.500.800.7525.0018.7531.25一个开闭站、二个变电所、一个发电机房,按5+20+20+5kW空调是否计算,系数选择4132.01.000.800.75132.0099.00165.00地上室内步行街着火处防烟分区的排烟风机+后勤疏散走道的排烟风机火灾时全启动还是分区启动5390.01.000.800.75390.00292.50487.50只计入室内步行街的楼梯的加压风机(26步楼梯间)6134.00.300.800.7540.2030.1550.25地下室各防火分区送风机、排风机为消防/平时两用风机,故该部分不能切断,该部分排风机平时由CO2浓度控制,故系数取0.3地下消防/平时两用风机系数7123.01.000.850.62123.0076.23144.71除去商铺部分,车库按0.3W/㎡,其它的区域按1.3W/㎡,火灾时全楼疏散通道上的应急照明灯具和疏散指示系统投入0.3和1.3是实际项目计算值8110.01.000.800.75110.0082.50137.509160.01.000.800.75160.00120.00200.001090.01.000.800.7590.0067.50112.50111279.01130.20831.63K∑p=0.92同时系数是否为1K∑q=0.92同时系数是否为1玻璃冷却泵合计柴油机消防负荷计算表变电站及发电机房用电地上消防动力设备(排烟风机)设备名称慧云机房消防用电慧云机房安防用电地上消防动力设备(加压风机)地下室排烟兼排风应急照明喷淋泵消防水泵注:电动排烟窗、防火卷帘门、电动排烟窗、地下车库排水泵等属于短时或错时负荷,故计算时不计入;无消防电梯;1290.941039.78765.1012同时系数1279.0工程名称:设计号:计算人:外界气压、温度、湿度的校正系数B0.95一般取:0.9(海拔大于400米,温度大于35°地区,须查表确定)发电机所带保障负荷计算功率P∑1(kW)-设计计算得出发电机所带消防负荷计算功率P∑2(kW)1039.78设计计算得出发电机总负荷计算功率P∑=MAX(P∑1,P∑2)1039.78消防负荷/保障负荷取最大值发电机所带负荷综合效率η∑0.88一般取:0.82~0.88发电机额定功率因数cos¢0.80一般取:0.8按稳定负荷计算发电机的容量(KVA)SG1=P∑/(η∑*cos¢*B)1554.70尖峰负荷造成的电压、频率降低而导致的电动机功率下降系数Kj0.95一般取:0.9~0.95发电机允许短时过载系数KG1.50一般取:1.4~1.6发电机所带负荷最大电动机的额定功率Pmax(KW)160.00工程确定(手动输入)发电机所带负荷最大电动机的额定电流In(A)In=Pmax/(√3*U*COS¢)303.87最大电动机启动方式星三角启动设计决定(手动输入)启动电压与额定电压比值0.58查询《启动倍数查询表》最大电动机的起动倍数K2.31查询《启动倍数查询表》最大电动机的起动电流Ist(A)Ist=K*In701.94最大电动机的启动时的尖峰电流(A)Ijf=Ist+IcIc为除最大电机外的其它负荷的电流。2372.80最大电动机的启动时的最大启动容量Sm(KVA)1561.73按尖峰负荷计算发电机容量(KVA)SG2=(Kj/KG)*Sm/B1041.15发电机的暂态电抗Xd‘0.25一般取:0.25母线允许的瞬时的电压降ΔU0.25一般取:0.2~0.3导致发电机最大电压降的电动机的启动容量(kVA)SSt△=√3*U*Ist462.00按发电机母线允许电压降计算发电机容量(KVA)SG3=(1-△U)/△U*Xd’*SSt△/C364.74应选发电机容量Se(kVA)1555kVA实际选择发电机容量Pe(kW)及参数1244kW选择一台1250kW柴油发电机组结论B-01/03柴油发电机容量计算基本参数按稳定负荷计算发电机的容量按尖峰负荷计算发电机容量按发电机母线允许电压降计算发电机容量发电机非消防状态负荷供电范围功率Pe(kW)KxcosφtanφPjiQjsQcQjs'IjsSjsSb负载率tgφ2cosφ2超市应急照明300.30.80.7596.80.06.817.111.30.40超市消防风机平时状态00.60.80.7500.00.00.00.00.00.40北区商业应急照明2750.30.80.7582.561.90.061.9156.7103.10.40北区商业消防风机平时状态00.60.80.7500.00.00.00.00.00.40南区商业应急照明1180.30.80.7535.426.60.026.667.244.30.40南区商业消防风机平时状态00.60.80.7500.00.00.00.00.00.40南区车库应急照明1430.30.80.7542.932.20.032.281.553.60.40南区车库风机水泵平时状态1340.60.80.7580.460.30.060.3152.7100.50.40700250.2187.7乘以1.0700250.2187.7合计7000.360.7220.96250.2187.7111.775.9397.3261.50.360.94计算结果7000.360.7220.96250.2187.70.0187.7475.2312.8125025%0.360.94自然功率因数计算0.7732677935212.523676.9发电机1250发电机消防状态按计算负荷负荷供电范围功率Pe(kW)KxcosφtanφPjiQjsQcQjs'IjsSjsSb负载率tgφ2cosφ2超市应急照明300.50.80.751511.30.011.328.518.80.40超市消防风机消防状态750.50.80.7537.528.10.028.171.246.90.40北区商业应急照明2750.30.80.7582.561.90.061.9156.7103.10.40北区商业消防风机消防状态5990.50.80.75299.5224.60.0224.6568.8374.40.40南区商业应急照明1180.30.80.7535.426.60.026.667.244.30.40南区商业消防风机消防状态6080.50.80.75304228.00.0228.0577.4380.00.40南区车库应急照明1430.30.80.7542.932.20.032.281.553.60.40南区车库风机水泵消防状态2600.50.80.7513097.50.097.5246.9162.50.40消防泵36510.80.75365273.80.0273.8693.2456.30.3624731311.8983.9乘以1.024731311.8983.9合计24730.530.7220.961311.8983.9585.7398.12082.91370.90.360.94计算结果24730.530.7220.961311.8983.90.0983.92491.41639.81250131%0.360.94自然功率因数计算0.77326779967960.8650856.9发电机1250超市消防负荷10510.80.7510578.80.078.8199.4131.30.40北区消防负荷717.50.80.80.75574430.50.0430.51090.2717.50.40南区消防负荷1398.40.60.80.75839.04629.30.0629.31593.51048.80.40负荷供电范围功率Pe(kW)KxcosφtanφPjiQjsQcQjs'IjsSjsSb负载率tgφ2cosφ2超市消防最大负荷10510.80.7510578.80.078.8199.4131.30.40北区消防最大负荷6770.850.80.75575.45431.60.0431.61092.9719.30.40南区消防最大负荷10100.80.80.75808606.00.0606.01534.61010.00.4017921488.51116.3乘以1.017921488.51116.3合计17920.830.7220.961488.51116.3664.6451.72363.41555.50.360.94计算结果17920.830.7220.961488.51116.30.01116.32826.91860.61250149%0.360.94自然功率因数计算0.773267791246209.4837951.2发电机1250连续12500.950.80.751187.5890.62255.31484.4备用137510.80.7513751031.32611.41718.8
本文标题:04-柴油发电机负荷计算书
链接地址:https://www.777doc.com/doc-5093602 .html