您好,欢迎访问三七文档
风冷式冷水机冷媒R22电源3相380V冠品制冷设备制造有限公司地址:昆山市正仪东亭子路5号电话:400-6390-7000512-62714302http:使用说明书使用说明书目录一.产品特性······················································1二.机器组成部分··············································2三.工作流程图··················································3四.机器安装······················································4-7五.操作说明······················································8-9六.注意事项······················································10七.规格参数······················································11-12八.故障排除方法··············································13九.维护与保养··················································14十.主电路原理图··············································15-16十一.故障分析·······················································17一、产品特性冠品牌工业冷水机是我公司根据市场的需求推出的一系列崭新设计的产品,其规格有几十种,制冷范围从2494大卡到567300大卡,冷冻出水温度范围标准型7℃~30℃。特殊低温型-10℃~30℃。冷水机广泛应用于各种工业生产中(塑胶工业、电子工业、电镀工业、食品工业、医药工业、印刷工业等)。大大的提高产品的质量。产品的特点:★主机采用欧美日名牌压缩机,运行稳定可靠,效率高,噪音低。★意大利、德国等名牌水泵,压力大,稳定性高,恒久耐用。★电子数字式控制器,精度高,使用范围广。★完善的电气保护系统,具有缺相保护、错位保护、电流过载保护、高低压保护及水流开关保护等确保机组的正确运行。★水冷机组冷凝器采用壳管式,因为螺纹铜管,设计合理,换热效果好;风冷机组散热冷排由翅片加上行列铜管组成,制造时采用二次翻边翅片机械涨管工艺和先进换热器生产线,保证优质高效。★产品出厂时已调试好,用户只需按使用说明书进行电源线、冷却水、冷冻水管路连接,即可投入使用。产品的选择:水冷式冷水机换热效果好且受环境变化影响小,适应于水质较好且水资源丰富的环境。风冷式冷水机使用灵活方便,易于安装及维护,占地面积小,适用于水质较差或水资源紧张的环境。-1-二、机器部分组件以上组图仅供参考,请以实物为准-2-轴流风机不锈钢水箱,外覆绝热材料,储存循环水三、工作流程图-3-风冷式冷水机单机组工作流程图四、机器安装安装示意图1.机组安装到位后,才可连接电缆线。2.所有导线必须牢固连接。3.所有导线不得与运动部件接触或产生干涉。4.保证电源符合所有机组的要求,依铭牌所示。5.电源线的地线必须与系统地线牢固连接,注意确保人身安全。-4-A、安装注意事项风冷式冷水机最注重散热效果,故安装前请选择地基平稳,四周空气畅通,空气无污染,油气少之场所,遮雨棚最好离机台上方一米五以上,如使用时仍发现四周空气闷热,请加装抽风机,保持空气对流,或将排出热气以排风管将其排出室外,如此不但可使冷水机延长使用年限,并提高效率,降低成本。注意:安装机器的环境温度最好在43℃以下,以确保机器发挥最大效能。电源,负载及接地部分请依照相关规定施工。B、首次运转必须先检查下列事项是否正确:1.电源电压及相数是否符合型号规格,请对照铭牌所示,注:一般3HP以下的冷水机采用单项,电压220V,50HZ电源,3HP及3HP以上冷水机电源式采用三相,电压380-415V,50HZ电源,相位分别为R,S,T,接地线为PE。2.补给水入口是否已接通管路,并保持水源不得关。3.先将冷冻水箱加满水后方可启动水泵。4.请留意水泵及风扇马达运转是否逆向,(参考机身上的方向),如逆转须将电源位线中任意二相对换。C、操作步骤:1.首先将电源开关置于ON位置上。2.开启水泵开关,此时请注意冷冻水出入口球阀必须打开。3.最后开启冷却开关,经延时开关压缩机及风扇会自动运行,请查视及调节所需温度。-5-D、警告1.冷冻水泵不可在水箱内无水时运转(3HP以上冷水机水箱无水时水泵会自动停止运转,低水位灯会亮起及有警报);2.操作开关请尽量避免连续切换;3.水温达到设定温度时,风扇马达及压缩机会自动停止运行,此现象属正常现象;4.温度调节开关应避免设定在5℃以下,防止蒸发器结冰;5.为确保制冷效果,保持最佳状态,请每周清洁冷凝器翅片网。附注一当冷凝器散热不良时,压缩机效率低,运转电流增大,当高压升至每25kg/cm2,压缩机受高压开关保护跳脱,压缩机停止运转,散热不良高压过载指示灯亮,此时请检视:1)风扇马达是否有运转、风扇叶有否断裂;2)散热铝片是否不清洁或油污太厚;3)周围空气是否畅通或过热;4)机台是否太靠近墙壁,以上正常后再复位高压开关即可正常运转。附注二:冷媒不足处理方法:1.当水温5℃以上时,低压显示低于1.5kg/cm2时,即表示冷媒不足,一般我们必须先将漏冷媒的地方,进行补漏处理,再更换干燥剂,重新真空处理后,充注适当冷媒。2.当您发现漏冷媒部分浸于水中,请立即停止冷水机运行,速将水箱内水排除,尽快通知公司派员维修,以免压缩机将水吸入系统造成更严重损坏。-6-附注三:高低压是否正常1.压缩机正常运行时高压表显示13-18kgf/cm2为佳,但不得高于25kgf/cm2,当高压高于25kgf/cm2时,高压开关跳脱,请依附注一处理,低压以3-5kgf/cm2为佳,但不得低于1.5kgf/cm2,低压跳脱时请依附注二处理。(注意:若机器为特殊低温型,当冷冻水在0℃以下时,低压偏低,属于正常现象)。2.当压缩机运行时高压和低压两者差压极少或相等时,即表示压缩机本身阀片破损或断裂,请即停止运转并通知公司派人处理。3.请注意以上状况是当压缩机正常运转时,如没有运转高低压平衡仍属于正常状况。附注四:当压缩机因某种原因发生故障时,此时水泵如继续运行,可能造成水温急速升高,而当水温超过70℃时,机内水管及水泵轴封极可能被损坏造成漏水。附注五:当故障指示灯及保护开关全部正常,压缩机不能启动,请检查:1.温度开关是否调太高或损坏。2.切换开关是否损坏。3.防冻开关是否损坏。4.低压开关跳脱或损坏。5.压缩机过载保护器损坏或跳脱。6.电磁继电器线圈损坏及过载保护器损坏。7.如机型内无水箱,请检查冰水流量开关是否损坏。——以上控制开关或线路如有故障即令压缩机不能运转。-7-五、操作说明接通电源后,电源指示灯不亮或亮红灯,请将三相电源中任意两相对换A、操作步骤:1.首先将主电源开关置于ON位置上。2.按下控制面板上的“PUMP”键开启水泵,此时请注意冷冻水出入口球阀必须打开。3.最后按下压缩机开关“COMP1”(两台压缩机的冷水机还要按下COMP2,若只有单台压缩机,COMP2无效),风扇会自动运行,经延时开关压缩机启动,请查视及调节所需温度。4.关机时,请依反顺序操作即可。B、操作流程:1)接通电源后,系统开始10S倒数计时,面板上PV区显示版本,SV区显示时间。若没有按“SET”键,之后主程序开始工作。2)主程序延时期间,按“SET”键会提示输入密码,此密码权限属于厂家,用户不能自行修改。-8-电源POWERRUN运行ERROR故障COMP1压缩机1COMP2压缩机2复位泵UP压机1DOWN压机2设置停止Er01-逆相Er02-#1压缩机高压Er03-#1压缩机低压Er04-#1压缩机过载Er05-#2压缩机高压Er06-#2压缩机低压Er07-#2压缩机过载Er08-冷冻水流不足Er09-冷冻泵过载Er10-冷却水流不足Er11-冷却泵过载Er12-出水温度过低Er13-温度探头开路Er14-温度探头短路Er15-防冻故障Er16-水箱水位GW511C面板示意图PVSV3)主程序开始后,PV区显示实际温度,SV区显示设定温度。此时,按“SET”键可以修改当前设定温度,利用“UP”,“DOWN”修改,改完后按“SET”键退出。(温度锁定最低下限为+3℃)。4)若有故障,PV区显示“err”,SV区显示故障代码,请按控制面板右侧故障代码查找相应的故障(或依故障代码表2所示),按“RESET”键可以消音,排除故障后,请按“RESET”键复位。故障代码含义如“表2”所示。5)“COMP1”和“COMP2”是分别允许压机1,压机2开启的按键,压机若被允许开启,则相应键上的led指示灯被点亮;若不允许开启,则相应的压机不会开机,按键上的led灯也不亮,只有在机组运行的时候,“COMP1”和“COMP2”按键才有效,当“COMP1”和“COMP2”有效时,按下该键,对应的led灯亮,再按下led灯灭。6)指示灯:POWER是电源指示灯,RUN表示机组运行,COMP1表示压机1运行,COMP2表示压机2运行,ERROR表示有故障。C、控制说明1)开机流程:按“RUN”键启动机器:先开水泵——再开压机1,若有2台机,再开压机2.2)关机流程:按“STOP”键停止机器:关所有压缩机——延时(时间可设)——关冷却风机——延时(时间可设)——关冷冻泵。3)能量调节:a)只有一个压缩机:在升温过程中,当T≧TS+△T时启动压缩机;在降温过程中,当T﹤TS时停止压缩机。b)有2个压缩机:升温过程中,当T≧TS+△T/2时启动1台压缩机,当T≧TS+△T时启动第2台压缩机;在降温过程中,当T﹤TS+△T/2时只开1个压缩机,当T﹤TS时,压缩机全停。-9-六、注意事项1.在供电的同时不要试图拆卸任何电气单元,否则可能导致电击。2.在供电的同时不要触及任一端子或端子板,否则可能导致电击。3.不要试图拆卸、修理或修改任意单元,任安全警告何这样做的企图都可能导致误动作、火灾或电击。不要在下列场所使用机器:△温度或湿度超过规范中规定范围的场所。△有腐蚀性气体或易燃性气体的场所。△受冲击或震动的场所。△有尘埃(特别是铁末)或盐雾的场所。注意△暴露于水、油或化学物质的场所。△使用温度在0~3℃时请按1:10的比例加入乙二醇,以免出水结冰。!注意-10-七、规格参数(一)1、标准工况:冷冻水出水温度7度,回水温度12度,环境温度35度;2、机组安全工作范围:冷冻水回水温度9度到20度,环境温度21度~43度;3、如采用R134a或R407c等环保型制冷剂,可与厂家联系;4、外形尺寸仅供参考-11-型号GPA-U01U02U03U05U08U010D名义制冷量KW2.85.68.814.723.329.8Kcal/h240048007500126002003825628电源1P/220V/50Hz3P/380/50Hz机组总容量KW1.262.33.545.557.0510.45压缩机输入功率(KW)0.751.52.254.55.89制冷剂类型R22充注量0.81.52.33.863.8*2风扇功率(KW)0.120.150.190.30.50.5蒸发器水流量(m3/h)0.611.52.54.45进出水管径(DN)DN15DN25DN40冷冻水管径英寸1/21/2G1-1/4”G1”G1-1/2”G1½”冷冻水泵输入功率(KW)0.370.371.10.750.751.1扬程(m)302526403835重量kg60120150170220350
本文标题:风冷机说明书通用本
链接地址:https://www.777doc.com/doc-3207618 .html